Title: | Electric Fields due to A 500 kV Quadruple Circuit Transmission Line: Some Aspects Concerning Public Exposure |
Authors: | Prasad K.Y. Punekar G.S. |
Issue Date: | 2019 |
Citation: | 4th International Conference on Electrical, Electronics, Communication, Computer Technologies and Optimization Techniques, ICEECCOT 2019 , Vol. , , p. 332 - 335 |
Abstract: | Extra high voltage and Ultra high voltage transmission lines produce high intensity electric fields (E-fields). These high intensity E-fields, which are in the vicinity of such lines, would result into adverse effects on humans. E-fields at the ground level should be below a certain limit as specified by the International Commission on Non-Ionizing Radiation Protection (ICNIRP) guidelines from the point of view of public exposure. In the present study the E-fields due to the Quadruple circuit transmission line is estimated and analyzed. Finite element method is used to calculate the E-fields by placing the conductors at the permitted worst-case sag (8%) position for the chosen span. These results are compared with those available in the literature with 4 % sag. © 2019 IEEE. |
URI: | https://doi.org/10.1109/ICEECCOT46775.2019.9114550 http://idr.nitk.ac.in/jspui/handle/123456789/14769 |
Appears in Collections: | 2. Conference Papers |